Features | Mode | Electromagnetic | |
Type (wave form of the earth leakage sensed) | B | ||
Rated current In | 25,40,63,80,100A | ||
Poles | 2P,4P | ||
Rated voltage Ue | 2P 240V~, 4P 415V~ | ||
Insulation voltage Ui | 500V | ||
Rated frequency | 50/60Hz | ||
Rated residual operation current(I△n) | 30mA | ||
Rated residual making and breaking capacity (I△m) | 500(In=2540A) 630(In=63A) | ||
Short-circuit current Inc= I△c | 10,000A | ||
SCPD fuse | |||
Break time under I△n | ≤0.1s | ||
Rated impulse withstands voltage (1.5/50) Uimp | 4000V | ||
Dielectric test voltage at ind.Freq. for 1min | 2.5kV | ||
Electrical life | 2,000 Cycles | ||
Mechanical life | 4,000 Cycles | ||
Installation | Contact position indicator | Yes | |
Protection degree | IP20 | ||
Ambient temperature (with daily average≤35ºC) | -5ºC~+40ºC | ||
Storage temperature | -25ºC~+70ºC | ||
Terminal connection type | Cable/Pin-type busbar/U-type busbar | ||
Terminal size top/bottom for cable | 35mm2 18-3AWG | ||
Terminal size top/bottom for busbar | 35mm2 18-3AWG | ||
Tightening torque | 2.5Nm 22In-lbs | ||
Mounting | On DIN rail EN60715(35mm) by means of fast clip device | ||
Connection | Power supply in both directions | ||
Tripping Current Range | Lagging Angle | I△n>0.01A | I△n≤0.01A |
0° | 0.35I△n≤I△≤1.4I△n | 0.35I△n≤I△≤2I△n | |
90° | 0.25I△n≤I△≤1.4I△n | 0.25I△n≤I△≤2I△n | |
135° | 0.11I△n≤I△≤1.4I△n | 0.11I△n≤I△≤2I△n |